What Is Gas Interlock System

HOW GAS INTERLOCK SYSTEM WORKS

Cuts off gas flow in the event of kitchen extract fan failure. Now a mandatory requirement in most commercial kitchens

Sensors placed either side of the ductwork fan monitor air pressure. They are connected to an air differential switch, which is activated when the pressure difference changes. Alternatively the current taken by the fan can be monitored by a fan power sensor. The 230V GIS monitors this switch/sensor and in the event of fan failure will close the gas solenoid and cut off the gas flow to kitchen appliances.

WHEN IS A GAS INTERLOCK SYSTEM A MANDATORY REQUIREMENT?

  • On installation of a completely new extraction/ventilation canopy
  • On installation of a completely new gas pipework run
  • On installation of a completely new cook line or layout
  • With any fitting of Category 'B' equipment e.g. combination ovens, deep fryers, grills, charcoal griddles. This includes replacements to an existing layout

Important documents / notes for your consideration and reference:

  • Corgi Technical Bulletin - TB 130 BS 6173
  • Gas Supply (Installation and Use) Regulation GSIUR27-4
  • HSE Information sheet No. 23 – Gas Safety in Catering and Hospitality
  • HSE CIS Sheet No. 10 - (Rev. 1)
Gas Interlock System Requirements :: Flow Diagram

You will need one of these (Controller)

GIS Controller :: G01N :: View Product Details GIS Controller :: G02 / G03 :: View Product Details GIS Controller :: G02R / G03R :: View Product Details GIS Controller :: G04 / G05 :: View Product Details GIS Controller :: G06 :: View Product Details
G01N G02 / G03 G02R / G03R G04 / G05 G06

GIS Controller Feature Guide

FEATURES MODEL
Gas Interlock Panel G01N G02 G02R G03 G03R G04 G05 G06
Operates 2 Fans
Built-in Emergency Stop
Built-in (On & Off) Switch
Built-in Fan Speed Controllers
Built-in Fan Current or Power Sensors
Connections for ADS & FPS Units Integral to Unit Integral to Unit
Connections to Remote Emergency Stop
Connections to Fire Alarm Panel
Anti-Back Pressure Feature
Audible Alarm
Fan Soft Start

Extras (built in to some Controllers)

  • Air Differential Pressure Switch with 2 metres of tubing
  • Fan Power Sensor
  • Honeywell Gas Solenoid Valves for pipe sizes ½" to 4" (REQUIRED)
  • Remote Emergency Cut-Off Switch
  • Gas Proving System
GIS Controller Extras :: Air Differential Pressure Switches :: View Product Details GIS Controller Extras :: Fan Power Sensors :: View Product Details GIS Controller Extras :: Gas Solendoid Valves :: View Product Details GIS Controller Extras :: Emergency Switches :: View Product Details GIS Controller Extras :: Emergency Switches :: Mushroom Button :: View Product Details GIS Controller Extras :: Gas Proving System :: View Product Details
Air Differential Switch Fan Power Sensor Gas Solenoid Valve Cut-off Switch Cut-off Switch Gas Proving System

Taken back at end of life (GIS, GPS Units and FPS)Taken back at end of life (GIS, GPS Units and FPS)